Can a RadioPro IP Gateway use PoE or radio-site backup power?

Last updated:

The RadioPro IP Gateway does not use Power over Ethernet (PoE); it requires its specified power supply. Backup power can support the installation when it supplies the correct power to every component needed for the communication path.

The Gateway is not powered by PoE. Match its exact input specification; a nominal 12 V bus is not enough.
The Gateway is not powered by PoE. Match its exact input specification; a nominal 12 V bus is not enough. Open full-size diagram
Include the complete path in a backup-power plan
ComponentWhy it matters
Control-station radioProvides the RF transmit/receive path.
RadioPro GatewayConnects clients to that radio.
Switch, router and modem/backhaulCarry the local or remote IP connection.
Dispatcher PC and audio equipmentProvide the operator's working console.

A Gateway on a UPS cannot communicate through an unpowered radio or router. For remote access, include the site's WAN equipment and the remote dispatch position's own power/network dependencies.

Do not connect a Gateway directly to a radio site's nominal 12 V battery bus solely because its adapter is marked 12 V. Battery systems can operate at a higher charging voltage, and accepted DC input ranges differ by hardware configuration. Use the supplied adapter on a suitable AC UPS, or have the dealer specify an approved regulated DC arrangement for the exact unit.

Size backup duration from measured loads, including radio transmit demand. Test operation through an outage and restoration as part of the site's maintenance procedure. Backup power does not extend RF coverage or replace the site's separate redundancy plan.